Loading...

RE-120GR

Choose the best products in our company
Home / Product / Ravel  / Gas Suppression System / Panels / RE-120GR

RE-120GR


specification

  • Zone Disable (Isolation) facility with loop voltage cut off.
  • Resettable 24v DC output for 4 wire detectors.
  • Three 24V Sounder Output (Fire, after Cross zone,
  • after gas release).
  • Two mode operation facility (Auto / Manual).
  • Programmable Solenoid Output with ON and OFF Timer.
  • Programmable Main / Standby Cylinder output Facility.
  • Gas Inhibit and Instant release facility.
  • Manual Gas Release with or without timer.
  • Actuator pressure low sensing facility.
  • RS 485 Output for Repeater.

  • Zone Disable (Isolation) facility with loop voltage cut off.
  • Resettable 24v DC output for 4 wire detectors.
  • Three 24V Sounder Output (Fire, after Cross zone,
  • after gas release).
  • Two mode operation facility (Auto / Manual).
  • Programmable Solenoid Output with ON and OFF Timer.
  • Programmable Main / Standby Cylinder output Facility.
  • Gas Inhibit and Instant release facility.
  • Manual Gas Release with or without timer.
  • Actuator pressure low sensing facility.
  • RS 485 Output for Repeater.
Brand Model RE-120GR
Power
220-240 VAC, 50 Hz.
Wire size: 1.5 Sq. mm with 600V insulation
Battery (Lead Acid only)
Charging Voltage 28 VDC.
System Quiescent Current 80mA
Initiating Device Circuits (Zone Circuit)
All zones are Class B wiring
Normal Operating Voltage Nominal 24 VDC
Alarm Current 15 - 35mA
Short Circuit Current 40mA Maximum
Loop resistance 50 ohms Maximum
Notification Appliance Circuits (Sounder / Strobe Circuit)
1) Supervised
Operating Nominal Voltage 24 VDC
Operating Current 0.75A (Max)
2) Non - Supervised
Operating Nominal Voltage 24 VDC
Operating Current 0.3A (Max)
End-Of-Line Resistor 4.7K, 1/4watt