Brand Model | RE-25AR | ||
---|---|---|---|
Primary Power (RE-SMPS-4A-R1) | |||
120 - 220VAC ± 10%, 50 Hz, 2.5Amps. | |||
Stand by Power | 24V D.C (2 Nos of 12v, 7Ah (Max.) Sealed Lead acid battery) | ||
Operating Condition | Operating Temperature :0 - 49° C/32-120° F. | ||
Relative Humidity 93 ± 2% RH (non-condensing) at 25 ±2° C/77 ±3° F. | |||
Charging Circuit | |||
Charging Voltage 28.4V, ±0.2V With current 800mA (Max). | |||
D.C. Output: | |||
Supervised 24VDC regulated, 1A Max. (for 4 wire smoke detector) | |||
Common Four Form C Relays | |||
Relay Contact Rating: 2Amps @ 30 VDC, 0.5Amps
@ 125VAC. Power Factor: 0.6 |
|||
Dimension of the panel : | |||
450 x 340 x 120 mm ( length x height x width ) | |||
Initiating Device Circuits | |||
Normal Operating Voltage: 14 - 21 VDC | |||
Alarm Current: 15 - 30mA. | |||
Short Circuit Current: 45mA Maximum | |||
Standby Current: 7mA (2mA for Detectors) | |||
Releasing Agent Circuits | |||
Operating Nominal Voltage: 24VDC Special Application Current for RACs: 0.6A per circuit Line Drop: 1.8V End-Of-Line Resistor: 3K9, 1/2watt. |